Description
Technical Specification | ||
Code | CF1100VDS | CF1200VDS |
Description | 1 Loop Control Panel | 2 Loop Control Panel |
Standards | EN54 Pt2,1997, A1:2006, EN54 Pt4,1997
A1:2002, A2:2006, EN54 Pt13: 2005 |
EN54 Pt2,1997, A1:2006, EN54 Pt4,1997
A1:2002, A2:2006, EN54 Pt13: 2005 |
Specification | ||
Number of Loops | 1 | 2 |
Addresses per Loop | 200 | 200 |
Number of Conventional | 2 monitored for open and short circuit | 2 monitored for open and short circuit |
Sounder Circuits | (max 1.5A combined) | (max 1.5A combined) |
Auxiliary Fire Routing Equipment
Output (Monitored) |
24V dc 30mA (max) | 24V dc 30mA (max) |
Auxiliary Fire Protection Equipment
Output (Monitored) |
24V dc 30mA (max) | 24V dc 30mA (max) |
Auxiliary Fault Routing Equipment
Output (Monitored) |
12V dc 30mA (max) | 12V dc 30mA (max) |
System Operating Voltage | 24V dc (nom) | 24V dc (nom) |
Mains Input Supply | 230V ac +10% / -15% | 230V ac +10% / -15% |
Class Change Facility | Terminals for connection of external contacts, can also be instigated via input
interface |
Terminals for connection of external contacts, can also be instigated via input
interface |
Auxiliary Relay | 1 set of changeover contacts operate in
event of fire condition |
1 set of changeover contacts operate in
event of fire condition |
Output Ports | RS485, RS232 for connection of repeaters
etc |
RS485, RS232 for connection of repeaters
etc |
Standby Duration | Dependant on loop loading and battery
configuration |
Dependant on loop loading and battery
configuration |
Battery | 2 x 7Ah | 2 x 7Ah |
Environmental | ||
Operating Temperature | -5°C to +40°C | -5°C to +40°C |
Humidity (Non Condensing) | 0 to 75% RH | 0 to 75% RH |
Physical | ||
Construction | Back Box – Steel | Back Box – Steel |
Dimensions (H x W x D) | 375mm x 357mm x 95mm | 375mm x 357mm x 95mm |
Weight | 8kg | 8kg |
Ingress Protection | IP30 | IP30 |
Cable entries | Top: cable knockouts (20mm)
Back: cable aperture |
Top: cable knockouts (20mm)
Back: cable aperture |
System Networking | Fully Networkable up to 126 panels (re-
quires additional network card, per panel) |
Fully Networkable up to 126 panels (re-
quires additional network card, per panel) |
Reviews